Schneider TeSys Deca LRD02 0.16–0.25A Class 10A Thermal Overload Relay
Schneider Electric LRD02 is a differential thermal overload relay with an adjustable 0.16–0.25 A motor-current setting and class 10A tripping. It provides phase-loss sensitivity and one normally open plus one normally closed auxiliary contact for signalling. It mounts directly under compatible TeSys LC1D contactors; separate mounting needs the specified accessory. This relay does not replace short-circuit protection.
Key specifications
- Model: LRD02
- Range: TeSys LRD / TeSys Deca
- Product type: Differential thermal overload relay
- Thermal adjustment: 0.16–0.25 A
- Trip class: 10A, IEC 60947-4-1
- Compatible contactors: LC1D09, LC1D12, LC1D18, LC1D25, LC1D32, LC1D38
- Operational voltage: 690 V AC, 0–400 Hz, power circuit
- Insulation rating: 690 V IEC; 600 V UL/CSA, power circuit
- Tripping threshold: 1.14 ±0.06 × Ir, IEC 60947-4-1
- Phase-loss sensitivity: Trips at 130% of Ir in two phases with the third phase at zero
- Auxiliary contacts: 1 NO + 1 NC
- Auxiliary duty: 3 A at 120 V AC-15; 0.22 A at 125 V DC-13
- Controls: Thermal setting dial, test selector, reset and stop buttons
- Mounting: Under compatible contactor; rail/plate with specific accessories (separate mounting block not included)
- Connections: Screw-clamp power and control terminals; 1.7 N·m tightening torque
- Temperature compensation: −20 to +60 °C
- Dimensions (H × W × D): 66 × 45 × 70 mm
- Net weight: 0.124 kg
- Protection degree: IP20, IEC 60529
- Operating ambient temperature: −20 to +60 °C without derating
- Impulse withstand voltage: 6 kV
- Standards: EN/IEC 60947-4-1; EN/IEC 60947-5-1
Official Schneider Electric datasheet
Submit your RFQ. Our team will send a quotation confirming price and availability.