Schneider TeSys LRD LRD350 37–50A Class 10A Thermal Overload Relay
Schneider Electric LRD350 is a TeSys LRD Class 10A thermal overload relay with an adjustable 37–50A range for motor protection. It includes phase-failure sensitivity, a 1NO+1NC signalling pair, test/stop controls and selectable manual or automatic reset. It mounts beneath compatible LC1D40A, LC1D50A and LC1D65A contactors; separate rail or plate mounting requires the appropriate accessory. Short-circuit protection and the contactor are selected separately.
Key specifications
- Model: LRD350
- Series / type: TeSys LRD differential thermal overload relay
- Adjustment range: 37–50A
- Trip class: Class 10A, IEC 60947-4-1
- Application: Motor overload and phase-failure protection
- Compatible contactors: LC1D40A, LC1D50A and LC1D65A
- Tripping threshold: 1.14 ±0.06 × Ir, IEC 60947-4-1
- Phase-failure response: Trip at 130% of Ir in two phases with the third phase at zero
- Auxiliary contacts: 1NO (97–98) + 1NC (95–96)
- Signalling thermal current (Ith): 5A; utilization-specific switching rating applies
- Reset modes: Manual or automatic, selected to suit the control circuit; automatic reset can allow restart
- Controls: Test, stop and reset
- Mounting: Under contactor; rail/plate mounting with specific accessories
- Power operational voltage (Ue): 690VAC, manufacturer network-frequency range 0–400Hz
- Network: AC/DC; manufacturer network-frequency range 0–400Hz
- Power insulation voltage (Ui): 690V IEC; 600V UL/CSA
- Impulse withstand (Uimp): 6kV
- Temperature compensation: −20 to +60°C
- Protection degree: IP20, IEC 60529
- Operating ambient: −20 to +60°C without derating
- Storage ambient: −60 to +70°C
- Signalling conductors: Two 1–2.5mm² conductors: solid or flexible with/without cable ends
- Signalling terminal torque: 1.7Nm
- Standards: EN/IEC 60947-4-1 and EN/IEC 60947-5-1
- Signalling utilization ratings: 0.95A at 380VAC AC-15; 0.06A at 440VDC DC-13
- Associated signalling fuse: 4A gG or 4A BS
- Power terminals: EverLink BTR; single 1–35mm² conductor per datasheet
- Power terminal torque: 5Nm for 1–25mm² single or paired conductors; 8Nm for 35mm² or mixed 1–25mm² + 35mm² per installation sheet
- Power / signalling wire stripping: 16mm / 10mm per installation sheet
- Mounting dimensions: 55mm width; use S1B31092-02 drawing for the selected contactor-mounted or separate-mounted assembly
- Net weight: 375g