قاطع مصبوب شنايدر EasyPact EZC100N3100 ثلاثي 100 أمبير 15 كيلو أمبير

أرسل طلب عرض السعر، وسيزوّدك فريقنا بعرض يؤكد السعر والتوفر.

EZC100N3100 is a 3-pole, 100 A EasyPact MCCB with thermal-magnetic protection and 15 kA Icu at 400–415 V AC. Fixed backplate mounting, front connections, and IP20 protection. Price and availability are confirmed in the quotation.

Get Your Discount code

Get a special discount when you buy from our store via an exclusive discount code

Share this product:

Model

EZC100N3100

Range

EasyPact EZC

Poles

3P; 3 protected poles

Rated current

100 A at 40 °C

Trip unit

TM-D thermal-magnetic; 100 A rating at 50 °C

Breaking capacity (Icu)

15 kA at 400–415 V AC, 50/60 Hz; IEC 60947-2

Service breaking capacity (Ics)

7.5 kA at 400/415 V AC

Operational voltage

Up to 550 V AC, 50/60 Hz; 250 V DC under specified pole arrangements

Insulation voltage (Ui)

690 V AC

Impulse withstand (Uimp)

6 kV

Mounting

Fixed, backplate; front connections

Dimensions (H × W × D)

130 × 75 × 60 mm

Protection degree

IP20; IK07

Earth-leakage protection

Not included

GTIN/EAN

3303430300892

Schneider EasyPact EZC100N3100 3P 100A 15kA MCCB

The Schneider Electric EZC100N3100 is a three-pole EasyPact molded-case circuit breaker for distribution circuits. Its TM-D thermal-magnetic trip unit provides overload and short-circuit protection. The rated current is 100 A at 40 °C, with an ultimate breaking capacity of 15 kA at 400–415 V AC. It uses fixed backplate mounting with front connections.

Key specifications

  • Model: EZC100N3100
  • Range: EasyPact EZC
  • Poles: 3P; 3 protected poles
  • Rated current: 100 A at 40 °C
  • Trip unit: TM-D thermal-magnetic; 100 A rating at 50 °C
  • Breaking capacity (Icu): 15 kA at 400–415 V AC, 50/60 Hz; IEC 60947-2
  • Service breaking capacity (Ics): 7.5 kA at 400/415 V AC
  • Operational voltage: Up to 550 V AC, 50/60 Hz; 250 V DC under specified pole arrangements
  • Insulation voltage (Ui): 690 V AC
  • Impulse withstand (Uimp): 6 kV
  • Mounting: Fixed, backplate; front connections
  • Dimensions (H × W × D): 130 × 75 × 60 mm
  • Protection degree: IP20; IK07
  • Earth-leakage protection: Not included
  • GTIN/EAN: 3303430300892

Official Schneider Electric datasheet

Submit your RFQ. Our team will send a quotation confirming price and availability.

Model

EZC100N3100

Range

EasyPact EZC

Poles

3P; 3 protected poles

Rated current

100 A at 40 °C

Trip unit

TM-D thermal-magnetic; 100 A rating at 50 °C

Breaking capacity (Icu)

15 kA at 400–415 V AC, 50/60 Hz; IEC 60947-2

Service breaking capacity (Ics)

7.5 kA at 400/415 V AC

Operational voltage

Up to 550 V AC, 50/60 Hz; 250 V DC under specified pole arrangements

Insulation voltage (Ui)

690 V AC

Impulse withstand (Uimp)

6 kV

Mounting

Fixed, backplate; front connections

Dimensions (H × W × D)

130 × 75 × 60 mm

Protection degree

IP20; IK07

Earth-leakage protection

Not included

GTIN/EAN

3303430300892