Schneider EasyPact EZC100N1100 1P 100A TM-D MCCB
Schneider Electric EZC100N1100 is a single-pole EasyPact EZC100N moulded-case circuit breaker with a100A TM-D thermal-magnetic trip unit. It provides overload and short-circuit protection with positive contact indication. Breaking capacity depends on voltage:18kA Icu at220–240VAC,2.5kA at380–415VAC and5kA at125VDC. It mounts on a backplate and has no built-in earth-leakage protection.
Key specifications
- Model: EZC100N1100
- Range / frame: EasyPact EZC100N
- Type: Moulded-case circuit breaker; distribution
- Poles / protected poles: 1P /1 protected pole
- Rated current (In): 100A at40°C
- Trip unit / rating: TM-D thermal-magnetic /100A at50°C
- Protection: Overload and short circuit
- Breaking-capacity code: N
- Rated operational voltage: 415VAC50/60Hz;125VDC, subject to voltage-specific capacities
- Icu / Ics at110–130VAC: 25 /12.5kA
- Icu / Ics at220–240VAC: 18 /9kA
- Icu / Ics at380VAC: 2.5 /1.25kA
- Icu / Ics at400–415VAC: 2.5 /1.25kA
- Icu / Ics at125VDC: 5 /2.5kA,1P
- Capacity standard: IEC60947-2; AC50/60Hz
- Insulation voltage (Ui): 690VAC50/60Hz
- Impulse withstand (Uimp): 6kV
- Isolation / utilization category: Suitable for isolation, IEC60947-2 /CategoryA
- Mounting: Fixed on backplate; front top and bottom connections
- Control / signalling: Toggle /positive contact indication
- Connection pitch: 25mm
- Mechanical durability: 13,000 cycles
- Earth-leakage protection: Without
- Dimensions (H × W × D): 130 ×25 ×60mm
- Protection degrees: IP20, IEC60529 /IK07, IEC62262
- Pollution degree: 3
- Operating / storage ambient: −25 to+70°C /−35 to+85°C
- Standards: EN/IEC60947-1, EN/IEC60947-2, GB/T14048.2, JIS C8201-2-2
أرسل طلب عرض السعر، وسيزوّدك فريقنا بعرض يؤكد السعر والتوفر.