Schneider Acti9 iC60H A9F84232 2P 32A C-Curve 10kA MCB
Schneider Electric A9F84232 is an Acti9 iC60H 2-pole C-curve thermal-magnetic circuit breaker rated 32A, with all 2 poles protected. It provides 10kA Icn at 400VAC under EN/IEC 60898-1 and 15kA Icu / 7.5kA Ics at 380–415VAC under EN/IEC 60947-2. Its 36mm DIN-rail body includes contact-position and trip indication. Observe voltage-specific AC/DC capacities; residual-current protection requires a separately selected compatible block.
Key specifications
- Model: A9F84232
- Series / type: Acti9 iC60H miniature circuit breaker
- Poles / protected poles: 2P / 2
- Rated current (In): 32A
- Trip technology / curve: Thermal-magnetic / C
- Magnetic tripping limit: 8 × In ±20%
- Icn, EN/IEC 60898-1: 10kA at400VAC, 50/60Hz
- Utilization category: Category A, EN/IEC60947-2
- Isolation suitability: Yes, EN/IEC60898-1 and EN/IEC60947-2
- Energy limitation class: 3, EN/IEC60898-1
- Insulation voltage (Ui): 500VAC, 50/60Hz
- Impulse withstand (Uimp): 6kV
- Indication: Contact-position indicator and trip indicator
- Mounting: Clip-on35mm DIN rail; removable with comb busbar installed
- Comb / distribution-block connection: Top or bottom, with compatible accessories
- Connection pitch / 9mm pitches: 18mm between phases /4
- Dimensions (H × W × D): 85 ×36 ×78.5mm
- Copper conductor terminals: Single conductor: rigid1–35mm²; flexible1–25mm² with/without ferrule
- Special terminal option: Designated accessories only:3×16mm² rigid copper,3×10mm² flexible copper,1×50mm² rigid aluminium or flexible copper/aluminium ring terminal
- Wire stripping / torque: 14mm /3.5Nm
- Mechanical / electrical durability: 20,000 /10,000 cycles
- Earth-leakage protection: Separate compatible block required; not included
- Add-on compatibility: Vigi iC60 single-terminal40/63A; Quick Vigi iC60 single-terminal40A, subject to full assembly selection
- Protection degree: IP20; IP40 inside modular enclosure, insulation classII
- Pollution / overvoltage category: 3 /IV
- Relative humidity: 95% at55°C
- Operating altitude: 0–2000m
- Operating / storage ambient: −35 to+70°C /−40 to+85°C
- Standards: EN/IEC60898-1 and EN/IEC60947-2
- Icu / Ics at12–133VAC: 42 /21 kA, EN/IEC60947-2,50/60Hz
- Icu / Ics at220–240VAC: 30 /15 kA, EN/IEC60947-2,50/60Hz
- Icu / Ics at380–415VAC: 15 /7.5 kA, EN/IEC60947-2,50/60Hz
- Icu / Ics at440VAC: 10 /5 kA, EN/IEC60947-2,50/60Hz
- Icu / Ics at≤125VDC: 15 /15 kA, EN/IEC60947-2; manufacturer-specified DC connection required
أرسل طلب عرض السعر، وسيزوّدك فريقنا بعرض يؤكد السعر والتوفر.